1.2. Terminal Identification and Electrical Ratings

Signal
Name
C
24AVAC Power Supply Common
R
24AVAC Power Supply
W1
Heat Stage 1, relay output
W2
Heat Stage 2, relay output
AUX
Dehumidification, relay output
O/B
Reversing Valve, relay output
Rc
24VAC Power Supply for Y1, Y2
Y1
Cool Stage 1, relay output
Y2
Cool Stage 2, relay output
ECO
Economizer, relay output
G
Fan Control, relay output
GND
Reference for DC Signals
B+
RS-485 B+ Signal
A-
RS-485 A- Signal
IN1
Remote 10K thermistor (Indoor)
IN2
Remote 10K thermistor (Outdoor)
IN3
Remote 10K thermistor (Supply)
IN4
Remote Humidity sensor (0-5V)
IN5
Fan proof input
GND
Reference for DC Signals
Table 1-2 - Terminal Identification and Electrical Ratings
2 • Emerson Programmable Touchscreen Thermostat I&O Manual
Description
Voltage
18-30VAC 50/60Hz
18-30VAC 50/60Hz
18-30VAC 50/60Hz
18-30VAC 50/60Hz
18-30VAC 50/60Hz
18-30VAC 50/60Hz
18-30VAC 50/60Hz
18-30VAC 50/60Hz
18-30VAC 50/60Hz
18-30VAC 50/60Hz
18-30VAC 50/60Hz
0-3.3VDC (10K NTC)
0-3.3VDC (10K NTC)
0-3.3VDC (10K NTC)
0-5VDC
0VDC or floating
Maximum Current
Rating
2.0A
2.0A
1.0A
1.0A
1.0A
1.0A
2.0A
1.0A
1.0A
1.0A
1.0A
026-1739 Rev 0