Temperature Recovery Time - Emerson VERDANT VX Series Installation Manual

Wired energy management thermostat with an occupancy sensor
Table of Contents

Advertisement

Custom Energy Savings Settings
10 – TEMPERATURE RECOVERY TIME
00-60
(25* default setting) Select the maximum time allowed for a PTAC
unit to attain temperature as defi ned by Heat and Cool "Recovery
Temperature";
"Temperature Recovery Time" selected here and the actual
temperature recovery ability of the PTAC unit are used to calculate
setback temperatures. Calculated setback temperatures maximize
energy savings and at the same time ensure that a comfortable room
temperature (defi ned as Heat and Cool "Recovery Temperature") will be
restored within the selected "Temperature Recovery Time".
Setting the "Temperature Recovery Time" to "00", disables temperature
recovery. When temperature recovery is disabled, thermostat will use
the Minimum and Maximum Setback Temperatures as setback set
points.