4. How to Programme
3-41 Ramp 1 Ramp Up Time
Range:
*
s
4
3-42 Ramp 1 Ramp Down Time
Range:
Size re-
lated
4.3. Parameter Lists
Changes during operation
"TRUE" means that the parameter can be changed while the frequency converter is in operation
and "FALSE" means that the it must be stopped before a change can be made.
4-Set-up
'All set-up': the parameters can be set individually in each of the four set-ups, i.e. one single
parameter can have four different data values.
'1 set-up': data value will be the same in all set-ups.
Conversion index
This number refers to a conversion figure used when writing or reading to and from the frequency
converter.
Conv. index
Conv. factor
46
Function:
[0.01 - 3600.00 s]
Enter the ramp-up time, i.e. the acceleration time from 0 RPM
to the rated motor speed n
time such that the output current does not exceed the current
limit in par. 4-18 during ramping. The value 0.00 corresponds
to 0.01 sec. in speed mode. See ramp-down time in par. 3-42.
Par
. 3 − 41 =
Function:
[0.01 - 3600.00 s]
Enter the ramp-down time, i.e. the deceleration time from the
rated motor speed n
down time such that no over-voltage arises in the inverter due
to regenerative operation of the motor, and such that the gen-
erated current does not exceed the current limit set in par. 4-18.
The value 0.00 corresponds to 0.01 s in speed mode. See ramp-
up time in par. 3-41.
Par
. 3 − 42 =
100
67
6
5
4
1
1/60
100000
100000 10000
0
MG.33.A9.02 - VLT is a registered Danfoss trademark
®
VLT
(par. 1-25). Choose a ramp-up
M,N
t
s
× n
acc
M
N
,
ref
Δ
(par. 1-25) to 0 RPM. Choose a ramp-
M,N
t
s x n
acc
M
N
,
Δ
ref
3
2
1
0
-1
-2
1000
100
10
1
0.1
0.01
AutomationDrive FC 300 Operating
Instructions
(
par
. 1 − 25 )
RPM
RPM
(
par
. 1 − 25 )
RPM
RPM
-3
-4
-5
-6
0.00
0.000
0.0000
0.000001
1
1
1