3.3. Electrical Installation
Aluminium Conductors
Terminals can accept aluminium conductors but the conductor surface has to be clean and the
oxidation must be removed and sealed by neutral acid-free Vaseline grease before the conductor
is connected.
Furthermore the terminal screw must be retightened after two days due to softness of the alu-
minium. It is crucial to keep the connection a gas tight joint, otherwise the aluminium surface will
oxidize again.
Tightening-up Torque
FC size
A1
A2
A3
A5
B1
B2
C1
C2
D1, D3
D2, D4
E1, E2
NB!
Cables General
All cabling must comply with national and local regulations on cable cross-sections
and ambient temperature. Copper (60/75°C) conductors are recommended.
200 - 240 V 380 - 500 V 525 - 690 V Cable for:
0.25-1.5 kW 0.37-1.5 kW
0.25-2.2 kW 0.37-4 kW
0.75-4 kW
3-3.7 kW
5.5-7.5 kW
5.5-7.5 kW
3-3.7 kW
5.5-7.5 kW
0.75-7.5 kW
5.5-7.5 kW
11-15 kW
11 kW
18.5-22 kW
15-22 kW
30-45 kW
30-37 kW
55-75 kW
-
90-110 kW
110-132 kW Line, motor cables
-
132-200 kW 160-315 kW Line, motor cables
-
250-400 kW 355-560 kW Line, motor cables
MG.33.A9.02 - VLT is a registered Danfoss trademark
-
Line,
Brake
resistor,
load sharing, Motor ca-
bles
-
Line,
Brake
resistor,
load sharing, Motor ca-
bles
Relay
Earth
-
Line,
Brake
resistor,
load sharing cables
Motor cables
Relay
Earth
-
Line,
Brake
resistor,
load sharing cables
Motor cables
Relay
Earth
-
Line,
Brake
resistor,
load sharing cables
Motor cables
Relay
Earth
Load Sharing, brake ca-
bles
Relay
Earth
Load Sharing, brake ca-
bles
Relay
Earth
Load Sharing, brake ca-
bles
Relay
Earth
3. How to Install
Tightening up torque
0.5-0.6 Nm
1.8 Nm
0.5-0.6 Nm
2-3 Nm
4.5 Nm
4.5 Nm
0.5-0.6 Nm
2-3 Nm
10 Nm
10 Nm
0.5-0.6 Nm
2-3 Nm
14 Nm
10 Nm
0.5-0.6 Nm
2-3 Nm
19 Nm
9.5 Nm
0.5-0.6 Nm
19 Nm
19 Nm
9.5 Nm
0.5-0.6 Nm
19 Nm
19 Nm
9.5 Nm
0.5-0.6 Nm
19 Nm
21
3