Option Card X57 - Danfoss MCO351 Technical Data Manual

Positioning controller
Hide thumbs Also See for MCO351:
Table of Contents

Advertisement

MCO351 Positioning Controller

2.3.1. Option Card X57

Terminal
1
2
3
4
5
6
7
8
9
10
Designation
Description
Touch probe switch
Interrupt triggered on the rising edge. If this signal
input
goes high when no touch probe target position is
currently locked a new touch probe target position
is calculated and locked in memory.
Positive HW limit
Interrupt triggered on the falling edge. Triggers a
switch input
HW limit error and the drive is stopped according to
P1906.
Negative HW limit
Interrupt triggered on the falling edge. Triggers a
switch input
HW limit error and the drive is stopped according to
P1906.
HOME
reference
Active high. Marks the HOME position in the appli-
switch input
cation.
Go to the refer-
Active high. Upon activation the drive goes to the
enced target posi-
specified target position. A low signal interrupts any
tion
positioning sequence. Not used in fieldbus mode.
Reset home flag
Active high. This input clears the home flag. This al-
lows the user to perform a second homing se-
quence. Not used in fieldbus mode.
Reset touch probe
Active high. This input clears the touch probe posi-
position
tion flag. The reset is necessary to carry out a touch
probe positioning command to a new target posi-
tion. Not used in fieldbus mode.
Quick stop
Active low. This input activates the Quick Stop func-
tion. The drive is stopped according to the setting of
P1906. After that the electromechanical brake is al-
ways activated when the "Quick stop" input is acti-
vated regardless of the P1906 setting.
Go to HOME posi-
While this input is high the drive executes the hom-
tion
ing sequence. While this input is high no position or
jog operations are carried out. Any homing se-
quence is interrupted by a low state on this input.
Not used in fieldbus mode.
LATCH new refer-
Active on the rising edge (must be "0" min. 1 ms. to
ence position index
guarantee edge detection): Latches reference posi-
number
tion index number specified on terminal 18, 19, 29,
32, 33 into memory. Digital output 4 – 8 is changed
to mirror the new reference index specified when
using digital input control. Not used in fieldbus
mode.