8.13.11 F_AVEX_R

Function
This block calculates the mean value from a maximum of nine inputs and then
outputs the result at the output. Inputs without a set validity bit are not included in
the mean value calculation. At least MIN inputs must be valid, otherwise the output
VALIDOUT will be reset.
I/Os
Name
Inputs:
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
VALIDIN1
VALIDIN2
VALIDIN3
VALIDIN4
VALIDIN5
VALIDIN6
VALIDIN7
VALIDIN8
VALIDIN9
MIN
Outputs:
OUT
VALIDOUT
Fail-Safe Systems
A5E00085588-03
Data Type
Explanation
F_REAL
Input variable 1
F_REAL
Input variable 2
F_REAL
Input variable 3
F_REAL
Input variable 4
F_REAL
Input variable 5
F_REAL
Input variable 6
F_REAL
Input variable 7
F_REAL
Input variable 8
F_REAL
Input variable 9
F_BOOL
IN1 valid
F_BOOL
IN2 valid
F_BOOL
IN3 valid
F_BOOL
IN4 valid
F_BOOL
IN5 valid
F_BOOL
IN6 valid
F_BOOL
IN7 valid
F_BOOL
IN8 valid
F_BOOL
IN9 valid
F_INT
Minimum number of valid
channels
F_REAL
Mean value
F_BOOL
Valid mean value
Default
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1
1
1
1
1
1
1
1
1
9
0.0
1