F_M_Do10 - Siemens SIMATIC S7 F Manual

Systems
Table of Contents

Advertisement

Fail-Safe Blocks
Error Information in Diagnostic Buffer
Error Code (W#16#...)
75DAH
8.6.5

F_M_DO10

Function
The F module driver reads the digital output values from the associated F channel
drivers (F_CH_DO) and writes them to a 10-channel, fail-safe digital output
module. In addition, it reads the error information of the module and makes the
data available to the associated F channel driver (F_CH_DO).
If there is a redundant module, the digital values are written to both modules.
The F module driver is automatically inserted at the end of the run-time group
which also contains the associated F channel driver F_CH_DO. The I/Os of the F
module driver are automatically interconnected and supplied with values.
The outputs DIAG_1 and DIAG_2, at which error information is output, are
important.
I/Os
Name
Inputs:
CHADDR00
...
CHADDR09
CRC_IMP1
CRC_IMP2
TIMEOUT
RED
LADDR
LADDR_R
8-66
Description
Error in the safety data format (error due to online modification of the Safety
Program or internal CPU fault)
Data Type
Explanation
F_WORD
Interconnection with the F
channel driver of channel 0
F_WORD
Interconnection with the F
channel driver of channel 9
WORD
CRC via implicit data SM1
WORD
CRC via implicit data SM2
(only when RED = 1)
F_DINT
Monitoring time in ms for vital-
sign monitoring
F_BOOL
Module Redundancy
0: SM configured as non-
redundant
1: SM configured as redundant
INT
Logical address of the module
(SM1)
INT
Address of the configured
redundant SM2 module (only
when RED = 1)
Default
Interconnected
automatically
Interconnected
automatically
Supplied
automatically
Supplied
automatically
Supplied
automatically
Supplied
automatically
Supplied
automatically
Supplied
automatically
Fail-Safe Systems
A5E00085588-03

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7 fh