Configuration
Adding F-I/O's via CIR
To add a new F-I/O to your System follow these steps:
Configure the new F-I/O within HWCONFIG according to the manual, "How to
Modify the System during Operation wth CiR (handle it like a standard module)
Calculate the Monitoring Time for this F-Module (see "Calculate the Monitoring
Time for Communication between the F-CPU and the F-I/O") and use it to
update the Monitoring Time for this F-Module in HWCONFIG.
Modify your safety program (add safety logic, channel driver and module driver
for this module)
Deactivate safety mode (see "Deactivating Safety Mode")
Download your safety program
Download your configuration via CiR
Activate safety mode (see "Activating Safety Mode")
Deleting F-I/O's via CiR
To delete an already existing F-I/O from your System follow these steps:
Delete the F-I/O within HWCONFIG according to the manual, "How to Modify
the System during Operation with CiR" (handle it like a standard module)
Modify your safety program (delete safety logic, channel driver and module
driver for this module)
Deactivate safety mode (see "Deactivating Safety Mode")
Download your safety program
Download your configuration via CiR
Activate safety mode (see "Activating Safety Mode")
Note
You can only delete an existing F-I/O via CiR if the module was added to the
system via CiR.
Changing of an exisiting configuration of an F-I/O is not possible.
4-12
Fail-Safe Systems
A5E00085588-03