8.5.4

F_R_R

Function
This block safely receives 5 data items of the data type F_REAL sent from another
F-run-time group from the F_S_R block.
The received data comes to the outputs RD_R_xx for further processing by other
blocks.
The input S_DB must be connected with the output of the same name of the
sending block.
The input TIMEOUT must be assigned a value for monitoring the safety-related
communication. If an updated frame is not received during this time, the system
function SFC F_CTRL is called. See "Monitoring Safety-Related Communication
Between F Run-Time Groups".
Startup Characteristics
In the first cycle after a cold or warm restart, the block outputs the substitute values
configured at the SUBR_xx inputs. The output of the substitute values depends on
the configured execution times of the cyclic interrupts and occurs as long as the
value F_TRUE is at the output SUBS_ON, but only until the monitoring time
TIMEOUT elapses.
I/Os
Name
Inputs:
TIMEOUT
S_DB
SUBR_00
...
SUBR_04
Outputs:
SUBS_ON
RD_R_00
...
RD_R_04
8-52
Data Type
Explanation
F_TIME
Monitoring time in ms for vital-
sign monitoring
F_WORD
Instance DB no. of the
associated F_S_R
F_REAL
Substitute value for receipt
data 00
...
F_REAL
Substitute value for receipt
data 04
F_BOOL
Substitution values are output 0
F_REAL
Receipt data 00
...
F_REAL
Receipt data 04
Default
T#0 ms
0
0
0
0
0
Fail-Safe Systems
A5E00085588-03