Safety
Note
To check during operation whether the configured PROFIsafe monitoring times are
too short, you can insert in an ET 200M with fail-safe signal modules in safety
mode additional fail-safe signal modules in safety mode in which the configured
PROFIsafe monitoring time is lower. This is particularly advisable if the configured
PROFIsafe monitoring time that has to be checked is not much longer than the
minimum possible PROFIsafe monitoring time.
See Also
Configuring the Monitoring Times for F/FH Systems
7.4.2.3
Monitoring of Safety-related Communication between CPUs
Time monitoring takes place in the F_SENDR and F_RCVR and F_SENDBO and
F_RCVBO blocks respectively with the same monitoring time, which has to be
assigned parameters on both blocks (TIMEOUT).
To ensure that monitoring is not triggered in F_SENDR and F_SENDBO or in
F_RCVR and F_RCVBO when there are no errors, the TIMEOUT monitoring time
selected must be sufficiently long:
TIMEOUT > T CI,F_SEND + T CI,F_RCV + MAX(TDelay,F_SEND;
TDelay,F_RCV) + 2*TUSEND + MAX(MIN(TCiR, F_SEND;2500), MIN(TCiR,
F_RCV;2500))
Note the following:
Time
Description
TCI,F_SEND
Configured cycle time of the cyclic interrupt OB with the
call of F_SENDBO or F_SENDR
TCI,F_RCV
Configured cycle time of the cyclic interrupt OB with the
call of F_RCVBO or F_RCVR
TDelay,F_SEND
Maximum communication delay when the standby in
the FH system is updated with the call of F_SENDBO
or F_SENDR
TDelay,F_RCV
Maximum communication delay when the standby in
the FH system is updated with the call of F_RCVBO or
F_RCVR
TUSEND
Maximum response time of USEND
With 48 bytes of user data for F_SENDBO
With 88 bytes of user data for F_SENDR
7-12
Where to Find it?
HWCONFIG
CPU properties, "Cyclic
Interrupt, Execution"
HWCONFIG
CPU properties, "Cyclic
Interrupt, Execution"
Properties of the sender
CPU, "H Parameters" tab
Properties of the receiving
CPU, "H Parameters" tab
You can find information on
the Internet (see below)
Fail-Safe Systems
A5E00085588-03