Fail-Safe Blocks
8.8.2
F_LIM_LL
Function
This block monitors the input variable U for violation of the lower limit (U_LL). A
hysteresis can also be specified to avoid fluttering of the output QL in the event of
fluctuations in the input value.
U ≥ U_LL: In the event of violation of the lower limit, the output QL = 1.
U_LL < U ≤ (U_LL + HYS): QL remains unchanged in this range.
U > (U_LL + HYS): In the event of upper limit violation + hysteresis, the output
QL = 0.
The limit and hysteresis are also available as non-fail-safe data at the outputs
U_LL_O and HYS_O for further processing in the standard program. The
hysteresis can be used to avoid fluttering of QL if the input value U fluctuates by
the limit value U_LL.
If either input variable U, U_LL or HYS contains an invalid REAL number, the
Substitute Input (SUBS_IN) will be passed directly to the output (QL).
If an invalid REAL number is generated during the calculations involving U, U-LL
and HYS, the output QL=1.
The output QLN corresponds to the negating output QL.
Note
The non-fail-safe outputs can be made available to the standard program without a
conversion block.
I/Os
Name
Inputs:
U
U_LL
HYS
SUBS_IN
Outputs:
QL
QLN
U_LL_O
HYS_O
8-94
Data Type
Explanation
F_REAL
Input variable
F_REAL
Lower limit
F_REAL
Hysteresis
F_BOOL
Substitute Input
F_BOOL
1: Lower limit violated
F_BOOL
Negating output QL
REAL
Upper limit
REAL
Hysteresis
Default
0.0
100.0
0.0
0
0
1
100.0
0
Fail-Safe Systems
A5E00085588-03