Fail-Safe Blocks
8.3.1

F_SENDBO

Function
This block safely sends 20 data items of the F_BOOL data type to another CPU.
The data can be received there by the F_RCVBO block.
The data to be sent (e.g. outputs from other blocks) is stored at the inputs
SD_BO_xx.
The data is transferred via safety frames.
If you want to temporarily switch off a data interchange that has been established
between two CPUs in order to reduce the load on the bus, you can assign the
value FALSE to the input EN_SEND. In this case, no more data is sent to the
recipient, and the recipient outputs the configured substitute values. If
communication between the connection partners was already established, when
data interchange restarted with EN_SEND = TRUE, an acknowledgment is
required on the recipient's side before the values sent are output again.
Startup Characteristics
After a startup (cold restart or warm restart), communication must first be
established between the communication partners. F_SENDBO indicates this at the
SUBS_ON parameter with "1". The recipient (F_RCVBO) outputs substitute values
during this time until communication between F_SENDBO and F_RCVBO has
started up via the safety frame and any acknowledgment required for reintegration
at F_RCVBO has been made.
I/Os
Name
Inputs:
EN_SEND
ID
R_ID
SD_BO_00
...
SD_BO_19
CRC_IMP
TIMEOUT
Outputs:
ERROR
SUBS_ON
RETVAL
Fail-Safe Systems
A5E00085588-03
Data Type
Explanation
BOOL
1 = switch transmission on
0 = switch transmission off
WORD
ID addressing parameter
DWORD
R_ID addressing parameter
F_BOOL
Send date 00
...
F_BOOL
Send date 19
DWORD
Address reference CRC
F_TIME
Monitoring time in ms for vital-
sign monitoring
F_BOOL
Transmission error
F_BOOL
Recipient outputs substitute
values
WORD
Error code
Default
1
0000
00000000
0
0
Supplied
automatically
T#0 ms
0
0
0000