2.To inspect the input
signal and it is stable.
Display
To inspect display function
[dsply]. It's maybe to be
shows "-----"
set to rs485
display value
1.To inspect display
function [dsply]. It's
dosen't
change
maybe to be set to
maXhd(maxmum hold)
or miNhd(minimum hold)
2.To inspect Down key
function [dNkey]. It's
maybe to be set to
pVhld.
Relay Output Issue:
PROBLEM
The
Check if the label of meter
perameters of
for detail specification.
Relay dosen't
shown
Relay cans
The relay energized, but
not action.
square red LED doesn't
bright
1.Check the energized
mode
2.Check the delay time and
delay band in the start
delay function.
3.Check the energized
delay time
The relay energized, but
square red LED dose
bright
1.Check the wiring of relay
output
2.Check the voltage of
supply power
Analogue Output Issue:
PROBLEM
Incorrection
1.To inspect the output
analogue
signal type (V/A/mA..) or
output value
range of meter whether
or out of
did match with signal in
accuracy
the field or not?
2.Check the Analogue
output high and low
setting.
26 / 30
CHECKING LIST
CHECKING LIST
CS1-RL(F) –OPERATION MANUAL(EN)-2013-01-04
A.Please try to set higher value in [ avg](A-12).
B.Please try to set higher value in [Dfilt](A-13).
C.Please connects a isolation transformer as close as meter in
power lines.
Please check the [dsply](A-07) in [input group] and
change the function setting from rs485 to
A.Please check the [dsply](A-07) in [input group] and
hange the function set from maXhd or miNhd to
A.Please check the [dNkey](A-14) in [input group] and
change the function setting from pVhld to
A. Please check the product number and output(O/P:_____)
description again for confirmation the relay output is
specified or not?
B. Please send back to our sales window, or order another
meter with relay function.
Please check the [ry!md](B-03) in the [relay group]
Please check whether did the [rYsb](B-01) is too wide and
[rYsd](B-02) is too long in [relay group] or not?
Please check whether did the [ry!rd](B-05) is too long in
[relay group] or not?
According to the label of meter, please check again the
connection wire of relay. Be careful to check the number of
relay is matching the setting.
A.Please check the product number and output(O/P:_____)
description again for confirmation the analogue output is
specified or not?;
B.Please confirm the output type is correct and check the range
in [AOtyp](D-01) of [Ao group]
A.Please check the [AOls](D-02) and [AOhs](D-03) in [ ao
group].
pv.
REMEDY
REMEDY
pv.
pv.