List Of Engineering Parameter Settings - Gree GMV-S120WL/A-S Service Manual

Dc inverter multi vrf units t1/r410a/50-60hz
Table of Contents

Advertisement

(1)
Press and hold "FUNCTION" button for 5 seconds and the temperature zone displays
"C00". Continue to press "MODE" button for 3 times, and then press and hold
"FUNCTION" button for 5 seconds to enter the interface of engineering parameter
settings. The temperature zone will display "P00".
(2)
Press " " or " " button to select a parameter code. Press "MODE" button to switch to
parameter value settings. The parameter value blinks. Adjust the parameter value by
pressing " " or " " button, then press "SWING/ENTER" button to complete the setting.
(3)
Press "SWING/ENTER" button to return to the previous step until exiting parameter
settings.
In the interface of engineering parameter settings, user can also set user parameters as listed
in table 3.2.
The engineering parameter setting list is as below:
Parameter
Parameter name
code
Power-off
P15
memory mode
Historical error
P17
clearing for
indoor unit
Setting of indoor
unit ambient
P20
temperature
sensor
P21
Corrected value
GMV5 Home DC Inverter Multi VRF Units
Table 3.4 List of Engineering Parameter Settings
Parameter range
00: Standby after
recovery from power
disconnection
01: Restore the
original status after
recovery from power
disconnection
00: Not cleared
01: Cleared
01: Temperature
sensor of air return
vent;
02: Temperature
sensor of wired
controller;
03: Temperature
sensor of air return
vent for cooling, drying
and fan mode;
Temperature sensor of
wired controller for
heating;
04: Temperature
sensor of wired
controller for cooling,
drying and fan mode;
Temperature sensor of
air return vent for
heating
-15~+15
Default value
00
It is to clear historical errors of all
00
When there are master and slave
temperature sensor of the master
wired controller is used by default.
03
temperature sensor setting is
invalid for a common indoor unit
sensor setting is invalid for a fresh
air indoor unit. The temperature
sensor of air return vent is used by
Press ―
Temperature
82
Remarks
indoor units controlled by the
current wired controller.
wired controllers and the
temperature sensor of wired
controller is used, only the
Note:
1. In auto mode, ambient
but the setting value is
memorized.
2. The ambient temperature
default.
‖ or ―
‖ to increase or