Note:
① The circuit breaker must support magnetic release and thermal release at the same time
to protect the system from short circuit and overload.
② The power cable specification means the selected specification when BV single-core
wire(2~4 pcs) goes through plastic pipe in ambient temperature of 40° C and the circuit
breaker operates in 40° C. If the actual installation condition changes, please refer to the
instruction manual for power cable and circuit breaker provided by the manufacturer.
③ The circuit breaker shall adopt D type circuit breaker.
④ The sectional area of a wire is applicable for a distance range of up to 15 m. If the
distance is greater than 15 m, increase the sectional area of the wire correspondingly to
prevent the wire from being burned due to overload current and to avoid fire.

12.2.2.2 Hydro box

The circuit breaker and power cable diameter of hydro box can refer to the following table:
Model
NRQD16G/A-S
Note:
① The power cable must be copper cable with operation temperature not higher than the
specified value.
② If the length of power cable is longer than 15m, please increase the sectional area of
power cable in order to avoid hazards caused by overload.
③ The power cable specification means the selected specification when BV single-core
wire(2~4 pcs) goes through plastic pipe in ambient temperature of 40° C and the circuit
breaker operates in 40° C. The circuit breaker shall adopt D type circuit breaker.
④ If the actual installation condition changes, please refer to the instruction manual for
power cable and circuit breaker provided by the manufacturer.

12.2.2.3 IDU

For information about the leakage circuit breaker for an indoor unit, refer to the following table.
The circuit breaker capacities listed in the following table indicate the circuit breaker capacities
when all indoor units in the same system are connecting connected to the main power.
Total capacity of
indoor units
below 10A
16~10A
GMV5 Home DC Inverter Multi VRF Units
Capacity of
Power supply
circuit breaker
Power supply
220V~50Hz
Capacity of circuit
breaker (A)
10
16
Min. sectional area
of grounding wire
2
(A)
(mm
20
2.5
25
2.5
Min. sectional area of
Capacity of
power cable (mm
circuit
Live
breaker (A)
wire
32
6
Min. sectional area of
2
power cable (mm
1.0
1.5
177
Min. sectional area
of power cable
2
)
(mm
)
2.5
2.5
2
)
Neut
Grounding
ral
wire
wire
6
6
Min. sectional area of
)
grounding wire (mm
1.0
1.5
2
)