System Function Button Operations; Introduction To Function Buttons - Gree GMV-S120WL/A-S Service Manual

Dc inverter multi vrf units t1/r410a/50-60hz
Table of Contents

Advertisement

Precautions:
A. When the DIP switch setting is not covered in the above scope, a DIP switch setting
exception fault may occur.
B. Only one fan can be set to emergency mode on a module.
C. The default factory setting is ―00‖.
D. The system cannot continually run for more than 120 hours in fan emergency operation
status. Once 120 hours are exceeded, the entire unit will be forcibly stopped and the
limited operation code ―Ad‖ is displayed on the IDU.
5) Outdoor Fan Static Pressure Setting DIP Switch (SA6_ESP_S)
The outdoor fan static pressure setting DIP switch (SA6_ESP_S) is used in special locations
such as the unit installation equipment room. In locations where air ducts are required to be
connected, zero static pressure, low static pressure, medium static pressure, and histatic pressure
can be set according to the design of air ducts. The setting methods are as follows:
The default factory setting is ―00‖.
6)Explanation of DIP switch positions
One the DIP switch, ―ON‖ indicates ―0‖ status and the opposite direction indicates ―1‖ status.
The position of white lever indicates the position to be set to.
Position of white lever
status

5.1.2 System Function Button Operations

Notes:
①System function settings and inquiry must be performed after commissioning of the entire
unit.
② System function settings and inquiry can be used no matter whether the entire unit runs.

5.1.2.1 Introduction to Function Buttons

The main board AP1 of the outdoor unit consists of eight function buttons:
GMV5 Home DC Inverter Multi VRF Units
Shielding the operation of 2#
0
1
Outdoor Fan Static Pressure Setting DIP
Switch (SA6_ESP_S)
DIP1
DIP2
Static Pressure Range
0
0
1
0
0
1
1
1
Position of white lever
status
224
fan
fan
0Pa
30Pa
50Pa
80Pa