System Faults; System Exhaust Temperature Exception - Gree GMV-S120WL/A-S Service Manual

Dc inverter multi vrf units t1/r410a/50-60hz
Table of Contents

Advertisement

Fan drive DC bus low
HL
voltage protection
H
Fan drive current detection
C
circuit fault
HJ

4.1.2 System faults

4.1.2.1 System exhaust temperature exception

GMV5 Home DC Inverter Multi VRF Units
1
Is the voltage of the input power cable
of the whole system lower than 320 V;
2Is the fan drive board well connected
with the compressor drive board;
3The fan drive board is faulty.
1
The fan drive board is faulty.
1
The drive board is damaged;
2
The fan's UVW cable is not connected
properly;
3
The fan is damaged.
270
1Elevate the voltage of the input
power cable to the required
range;
2Connect the fan drive board
with the compressor drive board
according to the wiring diagram;
3Replace the fan drive board.
1Replace the fan drive board.
1Replace the fan drive board;
2Reconnect the fan's UVW
cable;
3Replace the fan.