Table 5-2: Pressure Configuration via Class 2 Master (continued)
Steps
Select Measurement Type
Select Units
Enter Scaling
Set blocks to Auto
5.4
Host integration
5.4.1 Control host (Class 1)
The Rosemount 2051 device utilizes condensed status as recommended by
the Profile 3.02 specification and NE 107. See manual for condensed status bit
assignment information.
The appropriate GSD file must be loaded on the control host - Rosemount
2051 specific (rmt3333.gsd) or Profile 3.02 Generic (pa139700.gsd). These
files can be found on
5.4.2 Configuration host (Class 2)
The appropriate DD or DTM file must be installed in the configuration host.
These files can be found at EmersonProcess.com/Rosemount.
18 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flowmeter Quick Start Guide
Actions
Put Analog Input Block into Out of Service mode
Set Primary Value type to Pressure
Set Engineering Units
- Primary and secondary units must match
Set Scale In in Transducer Block to 0–100
Set Scale Out in Transducer Block to 0–100
Set PV Scale in Analog Input Block to 0–100
Set Out Scale in Analog Input Block to 0–100
Set Linearization in Analog Input Block to No
Linearization
Put Transducer Block into Auto mode
Put Analog Input Block into Auto mode
EmersonProcess.com/Rosemount
February 2019
or Profibus.com.