Emerson Rosemount 148 Quick Start Manual page 21

Temperature transmitter
Hide thumbs Also See for Rosemount 148:
Table of Contents

Advertisement

April 2019
Standards
used
Markings
Specific conditions of safe use (X):
1. See certificate for ambient temperature range.
2. The non-metallic label may store an electrostatic charge and become
a source of ignition in Group III environments.
3. Guard the LCD cover against impact energies greater than 4 joules.
4. Flameproof joints are not intended for repair.
5. A suitable certified Ex d or Ex tb enclosure is required to be connected
to temperature probes with Enclosure option "N".
6. Care shall be taken by the end user to ensure that the external
surface temperature on the equipment and the neck of DIN Style
Sensor probe does not exceed 266 °F (130 °C).
7. Non-Standard Paint options may cause risk of electrostatic discharge.
Avoid installations that cause electrostatic build-up on painted
surfaces and only clean the painted surfaces with a damp cloth. If
paint is ordered through a special option code, contact the
manufacturer for more information.
5.5.2
I7 IECEx Intrinsic Safety
Certificate
Standards used IEC 60079-0:2011, IEC 60079-11:2011
Markings
Special conditions for safe use (x):
1. The apparatus must be installed in an enclosure which affords it a
degree of protection of at least IP20. Non-metallic enclosures must
have a surface resistance of less than 1 GΩ; light allow or zirconium
enclosures must be protected from impact and friction when
installed.
Quick Start Guide
IEC 60079-0:2011, IEC 60079-1:2014-06, IEC
60079-31:2013
Ex db IIC T6...T1 Gb, T6(-50 °C ≤ Ta ≤ +40 °C), T5...T1(-50
°C ≤ Ta ≤ +60 °C);
Ex tb IIIC T130 °C Db, (-40 °C ≤ Ta ≤ +70 °C); IP66;
See
Table 5-1
for process temperatures.
IECEx BAS 08.0011X
Ex ia IIC T5/T6 Ga, T5(-60 °C ≤ Ta ≤ +80 °C), T6(-60 °C ≤ Ta
≤ +60 °C);
See
Table 5-2
for entity parameters.
Quick Start Guide
21

Advertisement

Table of Contents
loading

Table of Contents