Vega VEGABAR 86 Operating Instructions Manual page 45

Submersible pressure transmitter with ceramic measuring cell
Hide thumbs Also See for VEGABAR 86:
Table of Contents

Advertisement

Code
Cause
Text message
F264
Installation/Setup
error
F265
Measurement func-
tion disturbed
Tab. 7: Error codes and text messages, information on causes as well as corrective measures
Function check
Code
Cause
Text message
C700
Simulation active
Tab. 8: Error codes and text messages, information on causes as well as corrective measures
Out of specification
Code
Text message
S600
Impermissible electronics
temperature
S603
Impermissible operating
voltage
S605
Impermissible pressure
value
Tab. 9: Error codes and text messages, information on causes as well as corrective measures
Maintenance
Code
Cause
Text message
M500
Error in the delivery
status
VEGABAR 86 • Modbus and Levelmaster protocol
Inconsistent settings (e.g.:
distance, adjustment units with
application process pressure)
for selected application
Invalid sensor configuration
(e.g.: application electronic
differential pressure with con-
nected differential pressure
measuring cell)
Sensor no longer carries out a
measurement
A simulation is active
Cause
Temperature of the electronics in the
non-specified range
Operating voltage below specified
range
Measured process pressure below or
above the adjustment range
The data could not be restored
during the reset to delivery
status
8 Diagnosis, asset management and service
Rectification
Modify settings
Modify connected sensor con-
figuration or application
Carry out a reset
Disconnect operating voltage
briefly
Rectification
Finish simulation
Wait for the automatic end after
60 mins.
Rectification
Check ambient temperature
Insulate electronics
Use instrument with higher temperature
range
Check electrical connection
If necessary, increase operating voltage
Check nominal measuring range of the
instrument
If necessary, use an instrument with a
higher measuring range
Rectification
Repeat reset
Load XML file with sensor data
into the sensor
DevSpec
State in CMD 48
Bit 12 of Byte 0 ... 5
Bit 13 of Byte 0 ... 5
DevSpec
State in CMD 48
"Simulation Active"
in "Standardized
Status 0"
DevSpec
State in CMD 48
Bit 0 of
Byte 14 ... 24
45