Vega VEGABAR 86 Operating Instructions Manual page 29

Submersible pressure transmitter with ceramic measuring cell
Hide thumbs Also See for VEGABAR 86:
Table of Contents

Advertisement

Setup - Min. adjustment
Level
VEGABAR 86 • Modbus and Levelmaster protocol
6 Set up the sensor with the display and adjustment module
During adjustment, the pressure is entered e.g. for the level with full
and empty vessel, see following example:
Fig. 19: Parameter adjustment example "Min./max. adjustment, level measure-
ment"
1
Min. level = 0 % corresponds to 0.0 mbar
2
Max. level = 100 % corresponds to 196.2 mbar
If these values are not known, an adjustment with filling levels of e.g.
10 % and 90 % is also possible. By means of these settings, the real
filling height is then calculated.
The real product level during the adjustment is not important, because
the min./max. adjustment is always carried out without changing the
product level. These settings can be made ahead of time without the
instrument having to be installed.
Note:
If the adjustment ranges are exceeded, the entered value will not be
accepted. Editing can be interrupted with [ESC] or corrected to a
value within the adjustment ranges.
Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].
Now select with [->] the menu item "Adjustment", then "Min.
adjustment" and confirm with [OK].
2. Edit the percentage value with [OK] and set the cursor to the
requested position with [->].
3. Set the requested percentage value (e.g. 10 %) with [+] and save
with [OK]. The cursor jumps now to the pressure value.
2
100%
1
0%
29

Advertisement

Table of Contents
loading

Table of Contents