Hints on parameterization
Branch <device> – Basic System – I/O boards –
Board <x>: MFE7
Set the following values:
channel A1+ A1− or A2+ A2−: type Current input
parameter Power supply: value Off (sink mode)
6.4.8

HART Measurement Transmitter (EEx i) via ExMFE5 Board

Hazardous Area
HART pressure
transmitter, EEx i
HART temperature
transmitter, EEx i
Fig. 6-13: HART pressure and temperature transmitter (EEx i) via ExMFE5 – example
enCore FC
approx. 50 Ω
±0.05 % of the measurement
500 m
Safe Area
HART
communicator
Operating Instructions
Assembly Instructions
enCore device
ExMFE5 board
P+
P−
SH