Configuring Your Ethernet Connection; Connecting To The Controller Via Infrared Communications; Figure 4-3 Ir Communications Address - Honeywell 7866 Operation And Maintenance Manual

Triple range digital h2 and co2 analyzer/indicator and gas sampling panel
Table of Contents

Advertisement

Set Up Mode
4.9

Configuring your Ethernet Connection

Introduction
The P.I.E. Tool can connect to your controller via either Infrared (IR) or Ethernet communications port.
See sections 4.9.1 and 4.9.2. Only the P.I.E. Tool can be used to configure Ethernet parameters. The
figures in this section show screen-shots from the PC version of the P.I.E. Tool
Screens are generally similar in format but smaller.
This controller is shipped from the factory with the address for Infrared (IR) communications set to 3, the
Ethernet IP Address set to 10.0.0.2, the Ethernet Subnet Mask set to 255.255.255.0 and the Ethernet
Default Gateway set to 0.0.0.0. Consult your Information Technologies (IT) representative as to how these
should be configured for your installation. The MAC address is printed on the product label located on the
instrument's case.
The EUNPLGED message indicates the unit has an Ethernet card that is not connected to a network.

4.9.1 Connecting to the Controller via Infrared Communications

If connecting via IR and assuming that the instrument's IR address has not been changed from its factory
setting of 3, then configure your Communications Type as "Infrared" and your IR address to 3 as shown
below.
Select "PC COMM Setup", then select "Infrared". You cannot configure your Pocket PC for Ethernet.
Close the IR configuration window and then single click on the "Online Configuration" button.
42
7866 Triple Range Digital H

Figure 4-3 IR Communications Address

and CO
Analyzer/Indicator - Operation and Maintenance
2
2
®
Screens. Pocket PC
9/06

Advertisement

Table of Contents
loading

Table of Contents