Assembly Instructions
Characteristics MFE7:
two galvanically isolated input safe circuits for HF- or LF pulse
sensor
passive isolated pulse amplifier integrated in the inputs
a galvanically isolated input safe circuit for the direction signal;
a passive isolated pulse amplifier integrated in the inputs
max. input signal:
switching point
> 15 V DC:
< 6.5 V DC:
max. input frequency:
max. cable length depending on the operating mode:
message:
HF (up to 2 kHz):
HF (up to 5 kHz):
Hints on parameterization
Branch <device> – Basic System – I/O boards –
Board <x>: MFE7
Set following values:
channel D1+ GND: type HF pulse input channel A
parameter Flow direction detection: value On
channel D2+ GND: type HF pulse input channel B
Page 86 of 120
24 V DC
6 mA
(1)
(0)
5 kHz
500 m
250 m
100 m