The enCore FC is provided for assembly within a 19" cabinet, and is
available in either a 1/3 overall width or 1/2 overall width model. Compliance
with the device's installation depth of 170 mm (with plugs approx. 220 mm) is
necessary so the connection terminals located on the rear of the device
remain accessible.
The enCore FC must be installed in an Ex free plant room
(electrical room) outside of Ex zones 0, 1 and 2, in accordance
with protection class IP 20.
It is recommended that the enCore FC be installed in a swivel
frame.

6.1 Line Connection

WARNING!
Risk of explosion
A risk of explosion exists if lines are connected to the
ExMFE5 board while the device is connected to the power
supply!
Only connect transmitter, pulse and signal lines to the ExMFE5
board when power supply of the enCore FC is disconnected
completely.