Unit Dimensions - REMKO KWL 130 Operation Manual

Air-cooled chiller and air-cooled chiller with heat pump function
Table of Contents

Advertisement

REMKO KWL (H)
Working test for heating
mode
(only units with HP-function)
1. Switch the power supply on.
2. Open all shut-off valves if nec-
essary.
3. Switch the chilled water system
and the corresponding circulat-
ing pump to the highest stage.
The outlet temperature must lie
between +35 and +45°C.
4. Switch the unit on and select
the heating operating mode.
If the return temperature is
colder than the setting, the
compressor display will blink
and the compressor will begin

Unit dimensions

KWL 130(H) - 160(H)
430
155
KWL 270(H) - 320(H)
620
823
155
Vibration dampers sized in accordance with the different unit sizes are available as
accessories. Their dimensions must be added to the dimensions listed above.
36
to work after approx. 3 min-
utes.
5. Please note that the supply
temperature at the nominal
medium flow lies approx. 5 K
above the intake temperature.
- The circulation pump starts
and the controller checks the
medium flow over the flow
switch.
If the flow is insufficient, a
fault shut-down will be carried
out and the cooling cycle will
not work.
6. Measure and record all the
required values in the commis-
sioning report and check the
safety functions.
1220
Intake
Outlet
1195
1670
Intake
Outlet
823
KWL 180(H) - 220(H)
136
520
176
KWL 370 (H)
1160
195
All dimensions are given in mm
7. Check the system control using
the functions described in the
"Operation" chapter.
Final tasks
Reassemble all disassembled
parts.
Familiarise the operator with
the system.
NOTE
The system is delivered from
the factory with all parameters
set.
If during commissioning it is
necessary to change a param-
eter it can only be done by
authorised personnel.
1420
Intake
Outlet
1395
1535
Intake
Outlet
755
755