Summary of Contents for Danfoss VLT MCA 121 EtherNet/IP
Page 1
How to Control I/O Assembly Instances EtherNet/IP Connections Class 1 connection Class 3 connection Unconnected Messages, UCMM Control Word Profile Change of State, COS Danfoss FC Control Profile Danfoss FC Control Profile ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Other EtherNet Services Advanced EtherNet Settings Parameter List Data Types Data Types Supported by FC 200/FC 300 7 Troubleshooting Step-by-step Troubleshooting Alarm Word and Warning Word 8 Appendix Supported CIP Objects Index ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
In no event shall Danfoss be liable for direct, indirect, special, incidental, or consequential damages arising out of the use, or the inability to use information contained in this manual, even if advised of the possibility of such damages.
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load sharing (linkage of DC intermediate circuit), as well as the motor connection for kinetic back up. Please take note of discharge times and further safety guidelines from the section: “Safety and conformity”, in the respective Design Guide (MG.33.Ax.yy). ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
2.1.3 Assumptions These operating instructions are under the conditions that the Danfoss EtherNet/IP option is used in conjunction with a Danfoss FC 200/FC 300 frequency converter, inclusive that the installed controller supports the interfaces described in this document and that all the requirements stipulated in the controller, as well as the frequency converter, are strictly observed along with all limitations herein.
The VLT AutomationDrive IP21 / Type 1 Instruction provides information for installing the IP21 / Type 1 option. The VLT AutomationDrive 24 V DC Backup Instruction provides information for installing the 24 V DC Backup option. Danfoss Drives technical literature is also available online at www.danfoss.com/drives. 2.1.7 ODVA Conformance The EtherNet/IP option is tested to conform to the ODVA standards, and is certified, towards conformance test level version 3.
MCA 121 EtherNet/IP 3 How to Install 3 How to Install 3.1.1 The EtherNet/IP Option Illustration 3.1: Overview of the option ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
After installing the MCA 121 option, be aware of the following parameter settings: par. 8-01 Control Site : [2] Controlword only or [0] Digital and ctrl. word Control Word Source Option A par.8-02 : [3] ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Flashing red/green The EIP option is in self-test mode Green Table 3.2: NS1 + NS2: Network Status (one per port) During normal operation the MS and at least one NS LED will show a constant green light. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
For line topology please refer to section: “Recommended design rules” In a line topology all drives must be powered, either by mains or by their 24 V DC option cards, for the build-in switch to work. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
For connecting EtherNet/IP devices both hubs and switches can be used. It is, however, recommended always to use suitable industrial graded Ethernet IP Traffic switches. For more information regarding IP-switching, please refer to section: in this manual. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
It is not recommended to connect more than 32 drives in a line at any API. Exceeding the recommended design rules, may result in failing communication. AutomationDrive AutomationDrive AutomationDrive AutomationDrive AutomationDrive AutomationDrive AutomationDrive Max. 32 drives AutomationDrive AutomationDrive AutomationDrive AutomationDrive AutomationDrive AutomationDrive AutomationDrive ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
When crossing is unavoidable, the Ethernet cable must cross motor and brake resistor cables at an angle of 90 degrees. A utomationDrive ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Page 14
4 How to Configure MCA 121 EtherNet/IP ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
If no DHCP or BOOTP reply has been received after 4 attempts (e.g. if the DHCP/BOOTP server has been powered off), the option will fallback to the last good known IP address. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Half-duplex provides communication in both directions, but only in one direction at a time (not simultaneously). Full-duplex allows communication in both directions, and unlike half-duplex, allows for this to happen simultaneously. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
4 How to Configure 4.1.3 Configuring the Scanner EDS file Danfoss provides a generic English EDS (Electronic Data Sheet) file covering all voltage and power sizes, for off-line configuration. The EDS file can be downloaded from: http://www.danfoss.com/BusinessAreas/DrivesSolutions/Softwaredownload/DDFieldbus_Setup_Files.htm The current version of the major EtherNet/IP configuration tools does not support EDS-files for EtherNet/IP devices.
Page 18
– This button will make a simulated Power-cycle of the drive. EtherNet/IP Connections How to For more information on the CIP class 1 Forward Open command, please refer to section: under the Control -chapter. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Protocol costs change, the spanning-tree algorithm reconfigures the spanning-tree topology and re-establishes the link by activating the standby path. Spanning-Tree Protocol operation is necessary if the FC 200/FC 300’s are running in a ring/redundant line topology. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Page 20
5 How to Control MCA 121 EtherNet/IP ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
For configuration of a 2-word (32-bit) parameter read/write, use 2 consecutive arrays in par. 12-21 and 12-22, like [2]+[3], [4]+[5], [6]+[7] etc. Read/write of 2-word values in arrays like: [3]+[4], [5]+[6], [7]+[8] are not possible. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
ODVA; gives access to the ODVA specific profiles and assembly instances: 20, 21, 70 and 71 FC; enables the Danfoss profile and assembly instances: 100, 101, 103, 150, 151 and 153 For more information on the different profiles, please refer to the subsequent sections.
COS messages. If par. 12-37 is set to 0, the Production Inhibit Timer is disabled. The figure below shows the different PCD’s and their corresponding filter parameters. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
MCA 121 EtherNet/IP 5 How to Control 5.2 Danfoss FC Control Profile 5.2.1 Danfoss FC Control Profile Control Word according to FC ProfileDrive Profile. Instances 100, 101, 103/150, 151, 153 Preset Reference Select In par. 8-56 select a selection is made to define how Bit 00/01 gates with the corre- sponding function on the digital inputs.
Local operation Bus control Out of frequency limit Frequency limit ok No operation In operation Drive ok Stopped, auto start Voltage ok Voltage exceeded Torque ok Torque exceeded Thermal ok Thermal exceeded ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Bit = 0 Bit =1 Bit = 0 Bit =1 Stop Fwd Stop Run Fwd Stop Run Rev No function Fault reset No function Fault reset Net Ctrl Net Ref 07-15 ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Bit 0, Fault: Bit 0 = "0" means that there is no fault in the frequency converter. Bit 0 = "1" means that there is a fault in the frequency converter. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
If the bus speed reference is negative, and the control word contains a run reverse signal, the drive will run clockwise (- - is +). MAV is scaled in the same way as the reference. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
5.4.2 Bus Speed Reference Value under Instances 20/70 and 21/71 → The speed reference value should be transmitted to the VLT frequency converter in the form of a 16-bit word. The value is transmitted directly in RPM. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
LCP or via a digital input. Select setup 1 Changes the set-up upon reestablishment of communication following a control word time-out. If communication resumes causing the time-out situation to disappear, par.8-05 End-of-Timeout ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Page 32
Set in case of a trip, except if the trip is executed by an Alarm 68. [16] T37 DI status The bit indicates the status of terminal 37. “0” indicates T37 is low (safe stop) “1” indicates T37 is high (normal) ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Page 33
Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs. Control Site Digital and control word This parameter is active only when par.8-01 is set to [0] ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Page 34
Activates the Reverse command via the serial communication port or fieldbus option. Logic AND Activates the Reverse command via the fieldbus/serial communication port, AND additionally via one of the digital inputs. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Selects the IP Address assignment method. [0] * Manual IP-address can be set in par. 12-01 IP Address. DHCP IP-address is assigned via DHCP server. BOOTP IP-address is assigned via BOOTP server. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Range: Function: [00:1B:08:00:00:00 – 00:1B: Read only Displays the Physical (MAC) address of the option. 08:FF:FF:FF] 6.2.2 Ethernet Link Parameters 12-1* Ethernet Link Parameters Option: Function: Applies for whole parameter group. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Range: Function: [[0 - 9] PCD read 0 - 9] Configuration of readable process data. For configuration of 2-word (32-bit) parameter read/write, use 2 consecutive arrays in par. 12-21 and 12-22. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Reference from the network is not active. Reference from the network is active. 12-32 Net Control Option: Function: Read only. Displays the control source in Instance 21/71. [0] * Control via the network is not active. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Function: [0 – 9999] Configures the TCP port-number for the transparent socket channel. This enables FC-telegrams to be sent transparently on Ethernet via TCP. Default value is 4000, 0 means disabled. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
10% of the total bandwidth is allowed for broadcast messages, if the amount of broadcast messages increases above the 10% threshold, they will be blocked. Protection Value Port 1 (*Off – 20%) ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Page 41
Alignment Errors FCS Errors Single Collisions Multiple Collisions SQE Test Errors Deferred Errors Late Collisions Excessive Collisions MAC Transmit Errors Carrier Sense Errors [10] Frame Too Long [11] MAC Receive Errors ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
This number to the left refers to a conversion figure on the right to be used when writing or reading parameters. Conversion Index Conversion Factor 1/60 1000000 100000 10000 1000 0.01 0.001 0.0001 0.00001 0.000001 ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Warning word and alarm word are displayed in par. 16-90 to 16-95. For more information on the individual alarms and warnings, please refer to: FC 200/FC 300 Design Guide. Please note that the availability of the individual alarms and warnings are dependent on the drive type: /FC 200/FC 300 series. ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Page 46
Brake resistor short circuit 08000000 Brake chopper fault 10000000 Option change 20000000 Drive initialized 40000000 Safe Stop 80000000 Mech. Brake low MAR = Major Recoverable Fault MAU = Major Unrecoverable Fault ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Page 47
Low temperature 08000000 Reserved 08000000 Voltage limit 10000000 Reserved 10000000 Encoder loss 20000000 Reserved 20000000 Output frequency limit 40000000 PTC thermistor 40000000 Safe stop 80000000 Dangerous failure 80000000 Extended status word ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Danfoss Extended Control Output 4 Words Danfoss Extended Control Output 10 Words Danfoss Basic Control Input 2 Words Danfoss Extended Control Input 4 Words Danfoss Extended Control Input 10 Words Table 8.2: Instance Attributes ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Page 52
Bit 7 in FC CTW Alarm Word Fault Code UINT Mapping of par. 16-90 to CIP specific fault codes Control from net Boolean Parameter 12-31 value written from option Table 8.5: Instance Attributes ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Page 53
Sets the contents of specified attribute Reset Resets drive to it’s start-up state. Table 8.7: Services supported Control Word Profile Class ID 0x29 is only available if ODVA profile is selected in par.8-10 ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Page 54
Primary name server 12-06 [0] Name Server 2 UDINT Secondary name server 12-06[1] Domain Name STRING Default domain name 12-07 Get/Set Host Name STRING Host name 12-08 Table 8.10: Instance Attributes ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
Page 55
Human readable identification Link List Size USINT Number of members in Link List Link List ARRAY OF UINT Link List between internal and all according external interfaces Table 8.11: Instance Attributes ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
UINT parameter instance of base source offset link UINT parameter instance of offset source decimal precision USINT specifies parameter value format variable Table 8.14: Instance attributes ® MG.90.J2.02 - VLT is a registered Danfoss trademark...
UINT instance number of Parameter Object variable Table 8.16: Instance Attributes Class ID 0x64 – 0xC7 Danfoss Objects The CIP Class ID 100 to 199 (0x64 to 0xC7) gives access to all drive parameters. Class (decimal) Danfoss Parameter range 0-01 - 0-99 1-00 –...
Page 58
Supported Service Name Description of Service Class Instance Get_Attribute_Single returns contents of specified attribute Set_Attribute_Single modifies attribute Get_Att_Scattered returns specified parameter values Set_Att_Scattered sets specified parameter values Table 8.17: Services supported ® MG.90.J2.02 - VLT is a registered Danfoss trademark...