Assembly, Connection and Putting into Operation
If the automatic switchover of the pulse transducer (see chapter 5.2.1.4) is
used, adjust the necessary parameters as follows:
1. Adjusting the automatic switchover:
Move the cursor to the "Serv." register and to the value "Sc.Vm"
(sources for the volume at measurement conditions) via the following
path:
Serv.
Press the ENTER button.  The set value will start to flash.
Press one of the arrow keys  or  until the text "Input 2" starts to
flash.
Press the ENTER button to confirm the set value. The input value
can be deleted by pressing the ESC button.
2. Adjust the input mode of the high frequency pulse transducer:
Press the button  to display "Md.I2".
Press the ENTER button.  The set value will start to flash.
Press one of the arrow keys  or until the text "HF pulses" starts to
flash.
Press the ENTER button to confirm the set value. The input value
can be deleted by pressing the ESC button.
3. Adjust the cp value of the high frequency pulse transducer:
Press the button  to display "cp.I2".
Press the ENTER button.  The set value will start to flash.
Move the cursor using the arrow keys  or  to the digits and
change these using the arrow keys  or  to the cp value of the
pulse transducer connected to input 2.
Press the ENTER button to confirm the set value. The input value
can be deleted by pressing the ESC button.
4. Adjust the parameters for the low frequency pulse transducer:
Adjust the parameters for the low frequency pulse transducer on
input 1 as described in chapter 5.3.1.2.
Volume
Actual volume
Parameter settings
51
Sc.Vm