1.1 Introduction

1.1
Introduction
SICAM P38 & P39 3-phase Multi-function Power Meter integrate measurement, record, power metering,
remote communication and control, large screen LCD and network communication functions. This meter can
measure various parameters of power grid, such as voltage, current, power, power factor and frequency. It is
provided with 2
active and reactive energy. It has multi-tariff energy and multi-tariff demand functions. P38 has two independent
RS-485 ports; P39 has 1 RS-485 & 1 Ethernet port. Device supports MODBUS-RTU protocol (serial & TCP/IP).
Besides, it has binary input and output.
This product is extensively applicable to power substation and distribution automation system, industrial control
and industrial automation system, energy management system and community power monitoring, etc.
This 3-phase electronic multi-function power meter meets following standards:
• IEC 62052-11:2003 (Electricity metering equipment (a.c.) General requirements, tests and test conditions-
Part 11: Metering equipment) standard
• IEC 62053-22:2003 static meters for active energy (classes 0.2 S and 0.5 S)
• IEC 62053-23:2003 static meters for reactive energy (classes 2 and 3)
• Modbus-RTU
1.2

Features

This meter uses high-precision sampling and metering unit and high-speed MCU data processing unit, support-
ing high-precision, wide-range and accurate measurement and quick data analysis; segmented multi-line WVA
LCD, realizing various and abundant display; white backlight for LCD, satisfying the need for viewing data in
dark environment; NVRAM, supporting long-time data storage without data loss even in the event of power fail-
ure; high-precision clock chip with temperature compensation, ensuring accuracy of clock within operating tem-
perature range; double communication ports and industrial standard communication protocols, realizing flexible
and convenient networking; and different communication modules, satisfying different interface need of differ-
ent users.
8
nd
th
to 50
harmonic analysis and calculation of multiple power quality parameters. It can calculate
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018

Hide quick links: