2. Data items configurable with key (Note 1)
1
NO.
Symbol
1
2
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018
st
level menu
Definition
Symbol
Communi-
cation
setting
Ratio
setting
(Note 2)
nd
2
level menu
Definition
Range
Baud rate
600 ... 38400
Baud rate
600 ... 38400
8E1/8o1/8n1/8n
Parity
8E1/8o1/8n1/8n
Parity
Modbus address
0 ... 247
Modbus sending
0 ... 2999
delay
Reset Ethernet port
Ethernet communi-
cation module
2 ... 200
sending time inter-
val setting
Voltage ratio
0 ... 9999
integer part
Voltage ratio
0 ... 9999
decimal part
Current ratio
0 ... 9999
integer part
Current ratio
0 ... 9999
decimal part
Operation and Display
4.3 Key Definition
Remarks
Default setting:
2400
Default setting:
2400
Default setting: 8E1
2
Default setting: 8E1
2
Default setting: 0
Unit: ms
Default setting: 10
Unit: ms
Combination 0 ...
9999.9999
Default setting: 1
Combination 0 ...
9999.9999
Default setting: 1