Siemens SICAM P38 Manual page 64

3-phase power meter with multi-tariff function
Table of Contents

Advertisement

Communication
6.2.4 Information mapping table
Parameter
Record of previous
n events
Record of previous
50 events
Data bloak copy
Parameter
Phase A import active
power high 16 bits
Phase A import active
power low 16 bits
Phase B import active
power high 16 bits
Phase B import active
power low 16 bits
Phase C import active
power high 16 bits
Phase C import active
power low 16 bits
Total import active
power high 16 bits
Total import active
power low 16 bits
Phase A voltage
Phase B voltage
Phase C voltage
Average phase voltage
Uab line voltage
Ubc line voltage
Uca line voltage
Average line voltage
Phase A current
Phase B current
Phase C current
Average current
Neutral current
Phase A active power
Phase B active power
Phase C active power
Total active power
Phase A reactive
power
Phase B reactive
power
Phase C reactive
power
Total reactive power
64
Address
Data Type
...
52B9 H ...
unsigned int
52C1 H
Address
Data Type
7000 H
unsigned
long
7001 H
7002 H
unsigned
long
7003 H
7004 H
unsigned
long
7005 H
7006 H
unsigned
long
7007 H
7008 H
unsigned int 2 bytes
7009 H
unsigned int 2 bytes
700A H
unsigned int 2 bytes
700B H
unsigned int 2 bytes
700C H
unsigned int 2 bytes
700D H
unsigned int 2 bytes
700E H
unsigned int 2 bytes
700F H
unsigned int 2 bytes
7010 H
unsigned int 2 bytes
7011 H
unsigned int 2 bytes
7012 H
unsigned int 2 bytes
7013 H
unsigned int 2 bytes
7014 H
unsigned int 2 bytes
7015 H
signed int
7016 H
signed int
7017 H
signed int
7018 H
signed int
7019 H
signed int
701A H
signed int
701B H
signed int
701C H
signed int
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
Length
R/W
Same as previ-
Length
R/W
Data Range
4 bytes
R
0 ... 4294967295 0.1 Wh
4 bytes
R
0 ... 4294967295 0.1 Wh
4 bytes
R
0 ... 4294967295 0.1 Wh
4 bytes
R
0 ... 4294967295 0.1 Wh
R
0 ... 65535
R
0 ... 65535
R
0 ... 65535
R
0 ... 65535
R
0 ... 65535
R
0 ... 65535
R
0 ... 65535
R
0 ... 65535
R
0 ... 65535
R
0 ... 65535
R
0 ... 65535
R
0 ... 65535
R
0 ... 65535
2 bytes
R
-32767 ... 32767
2 bytes
R
-32767 ... 32767
2 bytes
R
-32767 ... 32767
2 bytes
R
-32767 ... 32767
2 bytes
R
-32767 ... 32767
2 bytes
R
-32767 ... 32767
2 bytes
R
-32767 ... 32767
2 bytes
R
-32767 ... 32767
E50417-H8940-C564-4, Release Date 06.2018
Unit/Descrip-
Data Range
tion
ous 1 event
Unit
0.01 V
0.01 V
0.01 V
0.01 V
0.01 V
0.01 V
0.01 V
0.01 V
0.001 A
0.001 A
0.001 A
0.001 A
0.001 A
1 W
1 W
1 W
1 W
1 var
1 var
1 var
1 var

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sicam p39

Table of Contents