6.2.4 Information mapping table
Instantaneous such as voltage, current, active/reactive and apparent power (4 Bytes formate)
Parameter
Phase A voltage higher
16 bits
Phase A voltage lower
16 bits
Phase B voltage higher
16 bits
Phase B voltage lower
16 bits
Phase C voltage higher
16 bits
Phase C voltage lower
16 bits
Average phase voltage
higher 16 bits
Average phase voltage
lower 16 bits
Uab line voltage higher
16 bits
Uab line voltage lower
16 bits
Ubc line voltage higher
16 bits
Ubc line voltage lower
16 bits
Uca line voltage higher
16 bits
Uca line voltage lower
16 bits
Average line voltage
higher 16 bits
Average line voltage
lower 16 bits
Phase A current higher
16 bits
Phase A current lower
16 bits
Phase B current higher
16 bits
Phase B current lower
16 bits
Phase C current higher
16 bits
Phase C current lower
16 bits
Average current higher
16 bits
Average current lower
16 bits
54
Address
Data Type
1800 H
unsigned
long
1801 H
1802 H
unsigned
long
1803 H
1804 H
unsigned
long
1805 H
1806 H
unsigned
long
1807 H
1808 H
unsigned
long
1809 H
180A H
unsigned
long
180B H
180C H
unsigned
long
180D H
180E H
unsigned
long
180F H
1810 H
unsigned
long
1811 H
1812 H
unsigned
long
1813 H
1814 H
unsigned
long
1815 H
1816 H
unsigned
long
1817 H
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
Length
R/W
Data Range
4 bytes
R
0 ... 9999999
4 bytes
R
0 ... 9999999
4 bytes
R
0 ... 9999999
4 bytes
R
0 ... 9999999
4 bytes
R
0 ... 9999999
4 bytes
R
0 ... 9999999
4 bytes
R
0 ... 9999999
4 bytes
R
0 ... 9999999
4 bytes
R
0 ... 99999999
4 bytes
R
0 ... 99999999
4 bytes
R
0 ... 99999999
4 bytes
R
0 ... 99999999
E50417-H8940-C564-4, Release Date 06.2018
Unit
0.001 V
0.001 V
0.001 V
0.001 V
0.001 V
0.001 V
0.001 V
0.001 V
0.0001 A
0.0001 A
0.0001 A
0.0001 A