Capacitor Module Connections - Allen-Bradley Kinetix 5500 User Manual

Hide thumbs Also See for Kinetix 5500:
Table of Contents

Advertisement

Chapter 5
Connect the Kinetix 5500 Drive System
Capacitor Module
Connections
104
Follow these guidelines when wiring the 2198-CAPMOD-1300 capacitor
module:
• Wire output (MS) connections to the Logix 5000™ controller
(optional).
• Refer to
Kinetix 5500 Capacitor Module
• Refer to
Kinetix 5500 Capacitor Module Status Indicators
for troubleshooting the module status indicator and relay output.
• Refer to the installation instructions provided with your Bulletin 2198
capacitor module, publication 2198-IN004.
IMPORTANT To improve system performance, run wires and cables in the wireways as
established in
shared-bus connection system.
Figure 59 - MS Connector Wiring
Table 50 - Capacitor Module Connector Specifications
Connector
Pin
Description
MS-1
Module Status
MS-2
PELV/SELV
CP-1
24V power (plug)
CP-2
DC-bus power
Bus-bar
(1)
DC bus connections are always made from one drive module to another over the shared-bus connection system. These terminals
do not receive discrete wires.
Rockwell Automation Publication 2198-UM001I-EN-P - May 2019
wiring example on
Chapter
2. Connections to the DC-bus must be made with the
2198-CAPMOD-1300
Capacitor Module
Module Status
2
(MS) Connector Plug
1
Recommended
Wire Size
Signal
2
mm
(AWG)
MS
0.14...1.5
MS
(28...16)
24V+
0.5...2.5
24V-
(20...14)
DC-
(1)
N/A
DC+
page
195.
on
page 159
Strip Length
Torque Value
mm (in.)
N•m (lb•in)
0.22...0.25
7.0 (0.28)
(1.9...2.2)
0.22...0.25
7.0 (0.28)
(1.9...2.2)
(1)
(1)
N/A
N/A

Hide quick links: