Chapter 2
Plan the Kinetix 5500 Drive System Installation
Kinetix 5500 Drive
Cat. No.
2198-H003-ERSx
2198-H008-ERSx
2198-H015-ERSx
2198-H025-ERSx
2198-H040-ERSx
2198-H070-ERSx
40
Table 14 - Power Dissipation Specifications
Frame
Size
20%
40%
1
12
25
2
40
80
3
64
128

Minimum Clearance Requirements

This section provides information to assist you in sizing your cabinet and
positioning your Kinetix 5500 drive:
• Additional clearance is required for cables and wires or the shared-bus
connection system connected to the top of the drive.
• Additional clearance is required if other devices are installed above and/
or below the drive and have clearance requirements of their own.
• Additional clearance left and right of the drive is required when
mounted adjacent to noise sensitive equipment or clean wire ways.
• The recommended minimum cabinet depth is 300 mm (11.81 in.).
Figure 14 - Minimum Clearance Requirements
Kinetix 5500
Servo Drive
Clearance left of the
drive is not required.
IMPORTANT
Rockwell Automation Publication 2198-UM001I-EN-P - May 2019
Usage as % of Rated Power Output
(watts)
60%
37
120
192
40 mm (1.57 in.) clearance above
drive for airflow and installation.
Clearance right of the
drive is not required.
40 mm (1.57 in.) clearance below
drive for airflow and installation.
Mount the drive in an upright position as shown. Do not mount the drive on its side.
80%
100%
50
62
160
200
256
320
Refer to the Kinetix Servo Drives
Technical Data, publication KNX-TD003,
for Kinetix 5500 drive dimensions.