Omron CJ1W- ECT21 Operation Manual page 73

Ethercat slave unit
Hide thumbs Also See for CJ1W- ECT21:
Table of Contents

Advertisement

Word
Bit
m + 10
08 to 15
08 to 15
m + 11
00 to 15
m + 12
00 to 15
*1. EM areas are not available for all CJ-series CPU Units. Refer to the operation manuals of the CPU Units for
details on the EM memory area specification.
CJ-series EtherCAT Slave Units Operation Manual (W541)
Name
Manipulated by
IN data area type
Unit
Reserved
---
First word in IN
Unit
data area
IN data area size
Unit
3 Memory Allocations
Default value
00 hex
The area type code in use is indi-
cated.
• 00 hex: not used
• 01 hex: CIO Area (CIO)
• 03 hex: Data Memory (DM)
• 04 hex: Work Area (WR)
• 05 hex: Holding Relay Area
(HR)
• 08 to 14 hex: Expansion Mem-
ory (EM) bank 0 to C
---
Reserved by system
0000 hex
The starting word of the IN data
area in use is indicated. The
ranges vary by IN data area
type.
• CIO: 0000 to 17FF hex
• DM: 0000 to 7FFF hex
• WR: 0000 to 01FF hex
• HR: 0000 to 01FF hex
• EM: 0000 to 7FFF hex
0000 hex
The IN data area size in use is
indicated. The value is in bytes
from one of the following.
• 00 hex: 0 byte
• 32 hex: 50 byte
• 64 hex: 100 byte
• C8 hex: 200 byte
• 190 hex: 400 byte
Function
*1
3
*1
3 - 15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac cj1w-ect21Sysmac cj series

Table of Contents