Omron CJ1W- ECT21 Operation Manual page 69

Ethercat slave unit
Hide thumbs Also See for CJ1W- ECT21:
Table of Contents

Advertisement

Word
Bit
m
00 to 07
08 to 15
m + 1
00 to 15
m + 2
00 to 15
m + 3
00 to 07
08 to 15
CJ-series EtherCAT Slave Units Operation Manual (W541)
Name
Manipulated by
OUT data area
User
type
Reserved
---
First word in OUT
User
data area
OUT data area
User
size
IN data area type
User
Reserved
---
3 Memory Allocations
Default value
00 hex
Set the area type code.
• 00 hex: not used
• 01 hex: CIO Area (CIO)
• 03 hex: Data Memory (DM)
• 04 hex: Work Area (WR)
• 05 hex: Holding Relay Area
(HR)
• 08 to 14 hex: Expansion Mem-
ory (EM) bank 0 to C
---
Reserved by system
0000 hex
Set the starting word of the OUT
data area. Setting ranges vary
by OUT data area type.
• CIO: 0000 to 17FF hex
• DM: 0000 to 7FFF hex
• WR: 0000 to 01FF hex
• HR: 0000 to 01FF hex
*1
• EM
: 0000 to 7FFF hex
0000 hex
Set the OUT data area size in
bytes from one of the following.
• 00 hex: 0 byte
• 32 hex: 50 byte
• 64 hex: 100 byte
• C8 hex: 200 byte
• 190 hex: 400 byte
00 hex
Set the area type code.
• 00 hex: not used
• 01 hex: CIO Area (CIO)
• 03 hex: Data Memory (DM)
• 04 hex: Work Area (WR)
• 05 hex: Holding Relay Area
(HR)
• 08 to 14 hex: Expansion Mem-
ory (EM) bank 0 to C
---
Reserved by system
Function
*1
3
*1
3 - 11