Bit
4
Unit Memory Error
5
ESC Error
6 to 15
Reserved
Unit Status 2 (n+11)
14 13 12 11 10 9
15
n + 11
Bit
0
Online Status
1 to 14
Reserved
15
Error Log Registered
CJ-series EtherCAT Slave Units Operation Manual (W541)
Name
Manipulated by
Unit
Unit
---
8
7
6
Name
Manipulated by
Unit
---
Unit
Unit operation
ON:
Indicates an error in internal memory where the error log or
I/O communication area data is stored. The error occurs
when the Unit starts up or when the error log is written.
OFF:
Indicates that the error did not occur. Once this error
occurs, the bit will remain ON and will not return to OFF.
Default: OFF
ON:
Indicates an error in ESC.
OFF:
Indicates that the error has not occurred. Once this error
occurs, the bit will remain ON and will not return to OFF.
Default: OFF
---
5 4
3
2
1
0
Online Status
Error Log Registered
ON:
Indicates that the Unit is online and capable of commu-
nicating on the network.
OFF:
Indicates that the Unit is offline.
A Unit will go offline under the following conditions:
• Operation is stopped by the hardware/software
check at startup.
• An ESC Error has occurred.
Default: OFF
---
ON:
Indicates that an error log was registered. Turns ON at
the first error log registration for the Unit.
OFF:
Indicates that no errors are registered in the error log.
Turns OFF when the Unit receives an error log clear
request.
Default: OFF