Omron CJ1W- ECT21 Operation Manual page 145

Ethercat slave unit
Hide thumbs Also See for CJ1W- ECT21:
Table of Contents

Advertisement

 Parameters
Name
Beginning record num-
ber (command)
Number of records
(command)
Maximum number of
stored records
(response)
Number of stored
records (response)
Number of read
records (response)
Error log data
(response)
 Error Log Data Format
1st byte
Error code Detailed
Name
Error code
Detailed information
Minute, Second, Day,
Hour, Year, Month
 Precautions
If the error log contains fewer records than the number specified in the number of records parame-
ter, all records stored in the error log at the time the command is executed will be returned and the
command executed will end normally.
 End Code
End code (hex)
0000
1001
1002
1103
110C
CJ-series EtherCAT Slave Units Operation Manual (W541)
Specify the first record to be read. The first record number can be specified in the range
between 0000 and 00F9 hex (0 to 249 decimal). The 0000 hex record is the oldest
record.
The number of records to read is specified between 0001 and 0063 hex (1 to 99 deci-
mal).
Indicates the maximum number of records that can be stored in the error log. The max-
imum number of error log records depends on the model of CPU Unit or CPU Bus Unit
being used. In an EtherCAT Slave Unit, the maximum number of stored records is fixed
at 00FA hex (250 decimal).
The number of records stored at the time the command is executed is returned.
The number of actual records read is returned as a hexadecimal value.
The specified number of error log records from the beginning record number is returned
sequentially. The total number of bytes in the error log is calculated as the number of
records x 10 bytes/record. Each error log record thus comprises 10 bytes. Refer to
Error Log Data Format on page A-31.
Min. Sec. Day Hour Year Month
infor-
mation
Details of the error stored in the record. Refer to 5-3-4 Error Log Error Codes on page
5-15 for details.
Indicates the time at which the error stored in the record occurred.
Normal end
Command too large
Command too small
Beginning record number is out of range
The number of read records is 0000 hex
Description
10th byte
Description
Description
Appendices
A
A - 31