7.5.4.2

Diagnostics via input image

Table 7- 41
Diagnostics input image
Byte
Bit7
d+0
count_2
d+1
Table 7- 42
Bit
7
6
5
4
3
2
1
0
Note
The "alive and well" counter is a 3 bit modulo counter on a PP application level. The PP
application can be monitored using this counter. Failure of the application software does not
generally result in a communication failure, as this is developed in a hardware-supported
manner. The watch dog switches off the digital outputs, while the inputs remain at their last
set values.
Table 7- 43
"alive and
well" counter
0
1
2
3 ... 7
PPU
Manual, 03/2013, 6FC5397-2DP40-3BA1
Bit6
Bit5
count_1
count_0
Messages in byte 0
Signal name
Message
count_2
alive and well 2
count_1
alive and well 1
count_0
alive and well 0
T_Alarm_2
Temperature not within the operating temperature range defined for the
module
T_Alarm_1
Critical temperature exceeded
Diag_2
Overload DO byte 5/4
Diag_1
Overload DO byte 3/2
Diag_0
Overload DO byte 1/0
Overview of messages as a function of the "alive and well" counter
Value
Message
byte 1
0
Reserved
Temperature value
0
No error
1
Impermissible input voltage in temperature measurement mode
2
Reserved
3
Overload at the outputs
4
Incorrect operating mode selection
5
Internal error, system error
6
Overrange at the inputs
7
Overrange at the outputs
0
Reserved
Bit4
Bit3
T_Alarm_2
T_Alarm_1
Status_1
Connectable components
7.5 PP 72/48D PN
Bit3
Bit1
Diag_2
Diag_1
Bit0
Diag_0
167