General Specifications - Omron E3NW-CCL User Manual

Cc-link digital sensor communications unit
Table of Contents

Advertisement

5 E3NW-CCL Hardware Specifications
5-2

General Specifications

This section gives the general specifications of the CC-Link Sensor Communications Unit.
Item
Unit power supply voltage
Power and current consumption
Indicators
Maximum connectable Sensors
Maximum connectable Distributed
Sensor Units
Vibration resistance (destruction)
Shock resistance (destruction)
Dielectric strength
Insulation resistance
Ambient temperature range
Ambient humidity range
Installation method
Weight (packed state/Unit only)
Materials
Accessories
*1 You can connect up to 16 Sensor Amplifier Units total to the Sensor Communications Unit and Distributed
Sensor Units.
*2 Temperature Limitations Based on Number of Connected Amplifier Units:
Groups of 1 or 2 Amplifier Units: 0 to 55°C, Groups of 3 to 10 Amplifier Units: 0 to 50°C, Groups of 11 to 16
Amplifier Units: 0 to 45°C
5 - 4
Specification and performance
24 VDC (20.4 to 26.4 V)
2.4 W max. (Does not include power supplied to Sensors.)
100 mA max. (Does not include current supplied to Sensors.) at 24 VDC
RUN indicator (green), ERROR indicator (red), and SS (Sensor Status)
indicator (green/red)
*1
16
8
10 to 60 Hz with a 0.7-mm double amplitude, 50 m/s
1.5 hours each in X, Y, and Z directions
2
150 m/s
for 3 times each in X, Y, and Z directions
500 VAC at 50/60 Hz for 1 min
20 MΩ min. (at 500 VDC)
*2
Operating: 0 to 55°C
Storage: −30 to 70°C (with no condensation or icing)
Operating and storage: 25% to 85% (with no condensation)
35-mm DIN Track-mounting
Approx. 180 g/approx. 80 g
Polycarbonate
Power Supply Connector, E3NW-DS Connector, DIN Track End Plates (2),
and Instruction Manual, Network connectors (2)
E3NW-CCL CC-Link Digital Sensor Communications Unit User's Manual (E431)
2
at 60 to 150 Hz, for

Advertisement