A-3 Command Response Time
(Reference Values)
The time required from when a command is sent to obtain the detection level of input 1 of Sensor
Amplifier Unit 1 connected to an E3NW-CCL Communications Unit until a response is received is
approximately 12 ms in Reduced I/O Mode, and approximately 18 ms in Monitor Mode.
* The command response time is a reference value only. Perform thorough testing in your own environment before
use. In Monitor Mode, you can read the detection levels in approx. 6 ms each if you use read/write registers.
Command response time = (1)
Test Conditions
Baud rate:
CPU Unit cycle time:
Number of CC-Link Slave Units:
CC-Link version:
CPU Unit
 Communications Configuration
Item
CPU Unit
CC-Link Master Unit
Sensor Communications Unit
Sensor Amplifier Unit
 Executed Command: Read Detection Level
Command number
Unit No.
E3NW-CCL CC-Link Digital Sensor Communications Unit User's Manual (E431)
10 Mbps
1 ms
1
Version 1 for Reduced I/O Mode
Version 2 for Monitor Mode
CC-Link Master Unit
Model number
Q02UCPU
QJ61BT11N
E3NW-CCL
E3NX-FA□0
20
01
Sensor Amplifier Unit
Communications Unit
Manufacturer
Mitsubishi Electric Corporation
Mitsubishi Electric Corporation
OMRON Corporation
OMRON Corporation
A Appendices
A
A - 21