3.3.2 Standalone Operation Connecting Air Flow Sensors to Air Flow Station

(1)
Air Flow Sensor Setting
Set the Unit No. and Termination resister of the Air Flow Sensor unit. Up to 8 Air Flow
Sensor units can be connected to an Air Flow Station, and it is possible to use
D6FZ-FGS1000 and D6FZ-FGT concurrently.
・ Set Unit No. from 01 in sequence.
・ When more than one sensor is connected with Air Flow Station, communication
terminator of the last sensor must be ON.
< D6FZ-FGS1000 >
This section shows the example of setting five Air Flow Sensor units.
(1) Open the switch cover by removing the screws on the Air Flow Sensor unit.
Remove Screws
Switch Cover
(2) Make settings on the 1st to 4th units.
DIP SW:
Rotary SW:
1:OFF
2:OFF
3:OFF
(3) Make settings on the 5th unit (termination).
DIP SW:
Rotary SW:
1:ON
2:OFF
3:OFF
Important
DIP SW and rotary SW settings are applied after the unit is reset.
Set the communication terminator (No. 1) to OFF on all the four
units.
See the figure below.
Assign ID numbers from 01 to 04.
10's Place 1's Place
0 (Fixed)
Set the communication terminator (No. 1) to ON.
Assign the ID to "05".
10's Place
0 (Fixed)
3-4
3. Check and Preparation
DIP SW
Rotary SW
・・・
1's Place