D6FZ-FGT
The following shows the supply pipe specifications.
Applicable diameter: D6FZ-FGT200 / 8A(Rc1/4)
Precautions for piping
When piping, fix with the part of conduit by wrench.
And secure piping with the tightening torque of the following list.
D6FZ-FGT200
D6FZ-FGT500
・ Fix with only the conduit part when piping. Do not fix with other parts, or the product
might be damaged.
・ When fixing with the part of flow channel by wrench, cover the body with something
like a waste cloth. If holding the body with a wrench directly, the body might be
damaged.
・ Check the flow direction before mounting pipes.
・ Do not apply force on other than conduit.
・ Make sure that foreign objects do not enter inside the body when piping.
・ Be sure to mount the body horizontally, otherwise the detection accuracy might be
worse.
・ Don't mount the body facing the control panel downward. Otherwise, the mist and
dust in the pipe accumulates and it might cause breakdown.
Model
Tightening torque
12 to 14N.m
31 to 33N.m
Flow Direction
3-27
3. Check and Preparation
D6FZ-FGT500 / 15A(Rc1/2)