Menu 5.9 - floor drying function
length of period 1 – 3, 5 – 7
Setting range: 0 – 30 days
Default value: 2 days
temp. period 1 – 3, 5 – 7
Setting range: 15 – 70 °C
Default value:
temp. period 1
temp. period 2
temp. period 3
temp. period 5
temp. period 6
temp. period 7
length of period 4
Setting range: 0 – 30 days
Default value: 3 days
temp. period 4
Setting range: 15 – 70 °C
Default value: 45 °C
Set the function for under floor drying here.
You can set up to seven period times with different
calculated flow temperatures. If less than seven periods
are to be used, set the remaining period times to 0
days.
Mark the active window to activate the underfloor
drying function. A counter at the bottom shows the
number of days the function has been active.
TIP
If operating mode "add. heat only" is to be
used, select it in menu 4.2.
Menu 5.10 - change log
Read off any previous changes to the control system
here.
The date, time and ID no. (unique to certain settings)
and the new set value is shown for every change.
NOTE
The change log is saved at restart and remains
unchanged after factory setting.
NIBE™ F370
5.12 - country
Select here where the product was installed. This allows
access to country specific settings in your product.
Language settings can be made regardless of this selec-
tion.
20 °C
30 °C
40 °C
40 °C
30 °C
20 °C
NOTE
This option locks after 24 hours, restart of dis-
play or program updating.
Chapter 8 |
Control - Menus
55