Nibe F370 Installer Manual page 41

Exhaust air heat pump
Hide thumbs Also See for F370:
Table of Contents

Advertisement

TIP
Wait 24 hours before making a new setting,
so that the room temperature has time to
stabilise.
If it is cold outdoors and the room temperature
is too low, increase the curve slope in menu
1.9.1.1 by one increment.
If it is cold outdoors and the room temperature
is too high, reduce the curve slope in menu
1.9.1.1 by one increment.
If it is warm outdoors and the room temperat-
ure is too low, increase the value in menu 1.1.1
by one increment.
If it is warm outdoors and the room temperat-
ure is too high, reduce the value in menu 1.1.1
by one increment.
Menu 1.2 - ventilation
Setting range: normal and speed 1-4
Default value: normal
The ventilation in the accommodation can be tempor-
arily increased or reduced here.
When you have selected a new speed a clock starts a
count down. When the time has counted down the
ventilation speed returns to the normal setting.
If necessary, the different return times can be changed
in menu 1.9.6.
The fan speed is shown in brackets (in percent) after
each speed alternative.
TIP
If longer time changes are required use the
holiday function or scheduling.
Menu 1.3 - scheduling
In the menu
scheduling
ilation) is scheduled for each weekday.
You can also schedule a longer period during a selected
period (vacation) in menu 4.7.
Menu 1.3.1 - heating
Increases or decreases in the accommodation temper-
ature can be scheduled here for up to three time peri-
ods per day. If a room sensor is installed and activated
the desired room temperature (°C) is set during the
time period. Without an activated room sensor the
desired change is set (of setting in menu 1.1). One step
is usually enough to change the room temperature by
one degree, but in some cases several steps may be
required.
NIBE™ F370
indoor climate (heating/vent-
Activated
SCHEDULING HEATING
schedule 1
activated
all
mon
tues
we
thur
21:30 - 06:00
fri
sat
sun
Day
Time period
Schedule: The schedule to be changed is selected here.
Activated: Scheduling for the selected period is activ-
ated here. Set times are not affected at deactivation.
System: Which climate system the schedule is for is
selected here. This alternative is only displayed if more
than one climate system is present.
Day: Select which day or days of the week the schedule
is to apply to here. To remove the scheduling for a
particular day, the time for that day must be reset by
setting the start time to the same as the stop time. If
the line "all" is used, all days in the period are set for
these times.
Time period: The start and stop time for the selected
day for scheduling are selected here.
Adjusting: How much the heating curve is to be offset
in relation to menu 1.1 during scheduling is set here.
If the rooms sensor is installed the desired room tem-
perature is set in °C.
Conflict: If two settings conflict with each other a red
exclamation mark is displayed.
TIP
If you wish to set similar scheduling for every
day of the week start by filling in "all" and then
changing the desired days.
TIP
Set the stop time earlier than the start time so
that the period extends beyond midnight.
Scheduling then stops at the set stop time the
day after.
Scheduling always starts on the date that the
start time is set for.
Schedule
System
1.3.1
schedule 2
schedule 3
system
20.5°
Conflict
Adjusting
Chapter 8 |
Control - Menus
39

Advertisement

Table of Contents
loading

Table of Contents