Output Electrical Specifications - Huawei UPS2000-A-6 kVA User Manual

Table of Contents

Advertisement

UPS2000-A-(6 kVA-10 kVA)
User Manual
Item
Input mode

9.5 Output Electrical Specifications

Item
Rated capacity
Output power factor
Rated output voltage
Output voltage
precision
Total harmonic
distortion of the
output voltage
waveform (THDv)
Crest factor
Issue 04 (2019-05-05)
6 kVA/10
kVA
Standard
Version with
Standard
Backup Time
minute. The input circuit breaker may trip in advance.
Load ≥ 150%: The UPS stops power output after 200 ms. The
input circuit breaker may trip in advance (load is calculated
based on the bypass currents).
Single mains
6 kVA/10
kVA
Standard
Version with
Standard
Backup Time
6 kVA/10 kVA
0.9 (When the power factor ranges from 0.5 to 1, the UPS2000-A
with inductive load is not derated. When the power factor ranges
from 0.5 to 1, the UPS2000-A with 80%–100% capacitive load is
linearly derated.)
220V AC/230V AC/240V AC
(selected by setting a voltage
level on the LCD.)
± 1%
≤ 5% (configured with a residual current device (RCD) with a
0.7 power factor, and specified in the IEC62040 standards of
THDv.)
≤ 2% (resistive load. Each harmonic meets the limit specified
by the IEC62040.)
A maximum of 3:1
Copyright © Huawei Technologies Co., Ltd.
6 kVA/10
6 kVA/10
kVA
kVA
Standard
Professional
Version
Version
with Long
with
Backup
Standard
Time
Backup
Time
6 kVA/10
6 kVA/10
kVA
kVA
Standard
Professional
Version
Version
with Long
with
Backup
Standard
Time
Backup
Time
208 V AC/220 V AC/230 V
AC /240 V AC (selected by
setting a voltage level on the
LCD. The power is derated to
0.9 in 208 V mode.)
9 Technical Specifications
6 kVA/10
kVA
Professional
Version
with Long
Backup
Time
6 kVA/10
kVA
Professional
Version
with Long
Backup
Time
118