Connecting Cables To The Ups Professional Version With Standard Backup Time - Huawei UPS2000-A-6 kVA User Manual

Table of Contents

Advertisement

UPS2000-A-(6 kVA-10 kVA)
User Manual
Step 3 Install AC output power cables and then AC input power cables, as shown in Figure 3-11.
Figure 3-11 Connecting cables to the UPS standard version with standard backup time
Step 4 Reinstall the UPS input and output wiring cover.
----End
3.2.3.2 Connecting Cables to the UPS Professional Version with Standard
Backup Time
Procedure
Step 1 Switch off the AC input and output circuit breakers at the rear of the UPS and the upstream
AC circuit breaker of the UPS.
Step 2 Remove the AC input and output wiring cover from the UPS.
Step 3 Install a short-circuit bar for a single UPS.
Step 4 Install AC output power cables and then AC input power cables, as shown in Figure 3-12.
A short-circuit bar is required only for a single UPS, but not a parallel system.
Issue 04 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
3 Installation
35