UPS2000-A-(6 kVA-10 kVA)
User Manual
Na
me
Fre
que
ncy
ran
ge
Sin
gle/
Par
alle
l
Issue 04 (2019-05-05)
LCD
Copyright © Huawei Technologies Co., Ltd.
Function
Value
Range
mode.
ECO
± 0.5 Hz,
frequency
± 1 Hz, ± 2
range. In
Hz, and ± 3
ECO mode,
Hz
when the
difference
between
the bypass
frequency
and the
rated
frequency
is greater
than this
range, the
system
determines
that the
ECO
frequency
is abnormal
and
transfers to
normal
mode.
The
frequency
range must
be less than
the bypass
frequency
range.
Set the
SIN (a
running
single
mode of a
UPS) and
UPS of the
PAR (a
professiona
parallel
l version.
system)
4 Control Panel
Preset
Remarks
Value
2 Hz
The value
is
configura
ble only
after the
inverter
shuts
down.
SIN
The value
is
configura
ble only
after the
inverter of
a UPS of
the
profession
al version
shuts
down.
72