Outdoor Main Pcb Abnormality - Daikin SkyAir RZR-TA Series Service Manual

Cooling only 60 hz heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

SiUS281811E

4.28 Outdoor Main PCB Abnormality

E1
Error Code
Applicable
All outdoor units
Models
Method of Error
Abnormality is detected under the communication conditions in the hardware section between the
Detection
indoor unit and outdoor unit.
Error Decision
When the communication conditions in the hardware section between the indoor unit and the
Conditions
outdoor unit are not normal.
Supposed
 Defective outdoor main PCB (A1P)
Causes
 Disconnection of the inside/outside relay wires
Troubleshooting
Part 6 Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn OFF the power once and
turn ON again.
Return to normal?
NO
Check if
inside/
YES
outside relay wires of
outdoor main PCB are
disconnected.
NO
YES
Troubleshooting by Error Codes
External factor other than
error (for example, noise
etc.).
Connect the inside/outside
relay wires correctly.
Replace the outdoor main
PCB (A1P).
221

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents