Advertisement

Field Settings from Outdoor Unit

2. Field Settings from Outdoor Unit

2.1

Capacity Setting

Caution
Be sure to carry out capacity setting after changing the main PCB (A1P) to spare PCB.
(for RZR30/36/42/48TAVJU and RZQ30/36/42/48TAVJU only)
Attach the capacity setting adaptor corresponding to capacity class to connector X51A.
Capacity setting is not required for RZR18/24TAVJU and RZQ18/24TAVJU.
RZR30/36/42/48TAVJU
RZQ30/36/42/48TAVJU
138
X51A
Model
Adaptor type
J56
Part 5 Field Settings and Test Operation
SiUS281811E